Backflow assembly test: Two Rivers Dental
ApprovedFiled Jul 11, 2026 by Drew Lindqvist, Ridge Backflow Testing. Filed from a phone.
Report
- Date of service
- Jul 11, 2026
- Assembly type
- RP
- Serial number
- W983469
- Size
- 1 1/2
- Test gauge serial
- G-8008
- Gauge calibration date
- Apr 10, 2026
- Check valve 1
- 7.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.2 psid
- Relief valve opened at
- 3.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Drew Lindqvist, current on the service date
- All required fields present
- Address matches parcel 097-21-01207
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
7037 Sycamore Way
Owner: Ellery Holdings LLC
Parcel 097-21-01207