Backflow assembly test: 113 Turkey Hill Ln
ApprovedFiled Oct 28, 2026 by Alex Kessler, Valley Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Oct 28, 2026
- Assembly type
- RP
- Serial number
- A855598
- Size
- 3/4
- Test gauge serial
- G-9806
- Gauge calibration date
- Oct 7, 2025
- Check valve 1
- 0.5 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 2.7 psid
- Relief valve opened at
- 3 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Alex Kessler, current on the service date
- All required fields present
- Address matches parcel 097-62-01169
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.