Back to the backflow review queue
Backflow assembly test: Golden Medical Offices
ApprovedFiled Nov 24, 2025 by Drew Okafor, Ridge Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Nov 24, 2025
- Assembly type
- RP
- Serial number
- A673776
- Size
- 1
- Test gauge serial
- G-6106
- Gauge calibration date
- Feb 1, 2025
- Check valve 1
- 4.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.8 psid
- Relief valve opened at
- 3.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Drew Okafor, current on the service date
- All required fields present
- Address matches parcel 097-45-01324
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
6922 Laurel Way
Owner: Benton Holdings LLC
Parcel 097-45-01324