Backflow assembly test: 6485 Pine Knoll Trl

Approved

Filed Aug 24, 2023 by Avery Stroud, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Aug 24, 2023
Assembly type
RP
Serial number
K495924
Size
3/4
Test gauge serial
G-7919
Gauge calibration date
Dec 14, 2022
Check valve 1
0.3 psid
Check valve 1 closed tight
No
Check valve 2
3.5 psid
Relief valve opened at
2.8 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Stroud, current on the service date
  • All required fields present
  • Address matches parcel 107-70-01322
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.