Back to the backflow review queue

Backflow assembly test: 6485 Pine Knoll Trl

Approved

Filed Sep 20, 2025 by Parker Fairley, Patriot Backflow Testing. Filed from a phone.

Report

Date of service
Sep 20, 2025
Assembly type
RP
Serial number
K495924
Size
3/4
Test gauge serial
G-8216
Gauge calibration date
Feb 26, 2025
Check valve 1
0.1 psid
Check valve 1 closed tight
No
Check valve 2
2.5 psid
Relief valve opened at
3.2 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Fairley, current on the service date
  • All required fields present
  • Address matches parcel 107-70-01322
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

6485 Pine Knoll Trl
Owner: Hayden Vance
Parcel 107-70-01322