Backflow assembly test: 9726 Sycamore Dr

Approved

Filed May 8, 2025 by Avery Stroud, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
May 8, 2025
Assembly type
RP
Serial number
A274774
Size
1
Test gauge serial
G-2466
Gauge calibration date
Nov 19, 2024
Check valve 1
8.2 psid
Check valve 1 closed tight
Yes
Check valve 2
2.7 psid
Relief valve opened at
3.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Stroud, current on the service date
  • All required fields present
  • Address matches parcel 107-82-01034
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.