Backflow assembly test: 4307 Hickory Ln

Approved

Filed May 6, 2026 by Avery Stroud, Valley Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
May 6, 2026
Assembly type
RP
Serial number
A665146
Size
3/4
Test gauge serial
G-3136
Gauge calibration date
Nov 11, 2025
Check valve 1
4.8 psid
Check valve 1 closed tight
Yes
Check valve 2
3.4 psid
Relief valve opened at
3.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Stroud, current on the service date
  • All required fields present
  • Address matches parcel 107-13-01133
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

4307 Hickory Ln
Owner: Quinn Whitcomb
Parcel 107-13-01133