Backflow assembly test: 4869 Turkey Hill Ct
ApprovedFiled Jun 5, 2026 by Morgan Pruitt, Valley Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Jun 5, 2026
- Assembly type
- RP
- Serial number
- Z405561
- Size
- 1
- Test gauge serial
- G-4082
- Gauge calibration date
- Oct 20, 2025
- Check valve 1
- 5.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.9 psid
- Relief valve opened at
- 3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Morgan Pruitt, current on the service date
- All required fields present
- Address matches parcel 107-65-01244
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.