Backflow assembly test: 3809 Stone Gate Dr

Approved

Filed Oct 30, 2025 by Riley Ramirez, Patriot Backflow Testing. Filed from a phone.

Report

Date of service
Oct 30, 2025
Assembly type
PVB
Serial number
K766101
Size
3/4
Test gauge serial
G-5490
Gauge calibration date
Oct 11, 2024
Check valve 1
0.4 psid
Check valve 1 closed tight
No
Check valve 2
3.8 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Riley Ramirez, current on the service date
  • All required fields present
  • Address matches parcel 107-54-01208
  • Test gauge calibration is more than a year old.
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.