Backflow assembly test: 8259 Fox Run Ln

Approved

Filed Jun 25, 2026 by Riley Ramirez, Patriot Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Jun 25, 2026
Assembly type
DC
Serial number
A580982
Size
3/4
Test gauge serial
G-2654
Gauge calibration date
Mar 4, 2026
Check valve 1
8.3 psid
Check valve 1 closed tight
Yes
Check valve 2
3.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Riley Ramirez, current on the service date
  • All required fields present
  • Address matches parcel 107-51-01001
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

8259 Fox Run Ln
Owner: Morgan Ashby
Parcel 107-51-01001