Back to the backflow review queue

Backflow assembly test: 3917 Turkey Hill Dr

Approved

Filed Apr 26, 2026 by Riley Ramirez, Patriot Backflow Testing. Filed from a phone.

Report

Date of service
Apr 26, 2026
Assembly type
RP
Serial number
W821176
Size
3/4
Test gauge serial
G-1218
Gauge calibration date
Dec 20, 2025
Check valve 1
7.4 psid
Check valve 1 closed tight
Yes
Check valve 2
1.1 psid
Relief valve opened at
3.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Riley Ramirez, current on the service date
  • All required fields present
  • Address matches parcel 107-36-01304
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

3917 Turkey Hill Dr
Owner: Jamie Lindqvist
Parcel 107-36-01304