Backflow assembly test: 6784 Stone Gate Dr

Approved

Filed Feb 26, 2026 by Riley Ramirez, Patriot Backflow Testing. Filed from a phone.

Report

Date of service
Feb 26, 2026
Assembly type
PVB
Serial number
K194708
Size
1
Test gauge serial
G-6785
Gauge calibration date
Nov 13, 2025
Check valve 1
4.2 psid
Check valve 1 closed tight
Yes
Check valve 2
3.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Riley Ramirez, current on the service date
  • All required fields present
  • Address matches parcel 107-42-01330
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.