Back to the backflow review queue

Backflow assembly test: Riverside Taqueria

Approved

Filed Oct 22, 2025 by Avery Stroud, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Oct 22, 2025
Assembly type
RP
Serial number
Z936351
Size
4
Test gauge serial
G-2953
Gauge calibration date
Dec 28, 2024
Check valve 1
5.5 psid
Check valve 1 closed tight
Yes
Check valve 2
2.1 psid
Relief valve opened at
2.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Stroud, current on the service date
  • All required fields present
  • Address matches parcel 107-91-01129
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

3802 Ridgeview Way
Owner: Nguyen Holdings LLC
Parcel 107-91-01129