Back to the backflow review queue

Backflow assembly test: 8924 Spring Branch Rd

Approved

Filed Aug 15, 2025 by Jordan Brandt, Summit Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Aug 15, 2025
Assembly type
PVB
Serial number
K993341
Size
3/4
Test gauge serial
G-2870
Gauge calibration date
Nov 29, 2024
Check valve 1
7.3 psid
Check valve 1 closed tight
Yes
Check valve 2
3.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jordan Brandt, current on the service date
  • All required fields present
  • Address matches parcel 107-55-01170
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

8924 Spring Branch Rd
Owner: Reese Danner
Parcel 107-55-01170