Back to the backflow review queue

Backflow assembly test: 3340 Orchard Dr

Approved

Filed Dec 7, 2025 by Morgan Pruitt, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Dec 7, 2025
Assembly type
RP
Serial number
K743360
Size
1
Test gauge serial
G-6258
Gauge calibration date
Jul 31, 2025
Check valve 1
8.8 psid
Check valve 1 closed tight
Yes
Check valve 2
1.1 psid
Relief valve opened at
2.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Morgan Pruitt, current on the service date
  • All required fields present
  • Address matches parcel 107-95-01229
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

3340 Orchard Dr
Owner: Jordan Wexler
Parcel 107-95-01229