Backflow assembly test: 6058 Hickory Way

Approved

Filed Jun 8, 2026 by Cameron Vance, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jun 8, 2026
Assembly type
DC
Serial number
W112031
Size
1
Test gauge serial
G-6695
Gauge calibration date
Mar 29, 2026
Check valve 1
3.3 psid
Check valve 1 closed tight
Yes
Check valve 2
4 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Cameron Vance, current on the service date
  • All required fields present
  • Address matches parcel 107-16-01093
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

6058 Hickory Way
Owner: Rowan Hollins
Parcel 107-16-01093