Backflow assembly test: Blue Heron Animal Hospital

Approved

Filed Jan 1, 2024 by Parker Vance, Summit Backflow Testing. Filed from a phone.

Report

Date of service
Jan 1, 2024
Assembly type
RP
Serial number
Z580768
Size
4
Test gauge serial
G-6853
Gauge calibration date
Mar 23, 2023
Check valve 1
5.9 psid
Check valve 1 closed tight
Yes
Check valve 2
3.1 psid
Relief valve opened at
3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Vance, current on the service date
  • All required fields present
  • Address matches parcel 107-75-01223
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.