Back to the backflow review queue

Backflow assembly test: 353 Stone Gate Ln

Approved

Filed May 18, 2025 by Avery Stroud, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
May 18, 2025
Assembly type
DC
Serial number
A211830
Size
1
Test gauge serial
G-5483
Gauge calibration date
Dec 19, 2024
Check valve 1
6.7 psid
Check valve 1 closed tight
Yes
Check valve 2
2.4 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Stroud, current on the service date
  • All required fields present
  • Address matches parcel 107-87-01327
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

353 Stone Gate Ln
Owner: Reese Ashby
Parcel 107-87-01327